Product Code
Example EM-EMB cat. 15.WW
MODEL NO | WATTAGE | TEST SWITCH |
EM-EMB | 15 15W/Up to 80W Driver | WW Wired |
| 25 25W/Up to 150W Driver | WL 2.4GHz Remote |
| 40 40W/Up to 300W Driver | |
NOTES
¹ The emergency driver is not compatible with non-dimmable fixtures when the driver wattages is less than the fixture wattage.
Self Diagnostic
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30 second and annual 90 minute tests to verify proper emergency capability per life safety code requirements NFPA 101 Life Safety Code outlines the following schedule:
Monthly
During AC mode, the system conducts a 30s self discharge test of the emergency LED driver every 30 days and automatically restores to normal charging after full discharge
Annually
During AC mode, the system conducts a 90 minute self discharge test of the emergency led driver every 365 days and automatically restores to normal charging after 30 seconds discharge
Operation
Normal Supply
During normal AC supply conditions the LED driver load will operate as usual and emergency driver remains in charging mode
Emergency Mode
When AC power fails the driver automatically switches to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. During this time, the indicator will flash slowly (light on for 2 seconds, off for 2 seconds). When AC power is restored, it will return to charging mode and the indicator light remains on
Specification
Input Voltage: 120-347VAC 50/60Hz
Input Power: 12W Max
Output Voltage: 170VDC
Output Power: 15,25,40W Power Factor: 0.85
EMI Radiated/Conducted: FCC Class A Charge and EM Modes
Surge Protection: Meets ANSI/IEEE C62.41.2-2002
Emergency Operation: 90 minutes
Charge Time: 24hr Recharge
Ambient Temperature: Lithium -25°C to +40°C (-13°F to 104°F)
Approval: cUL Listed for Factory and Field Installation
Applications
Linear highbays, high output troffers, panels and downlights