EM-HBM Series

Highbay Emergency Driver

LED Emergency Battery Backup for Sunled round or linear highbay lights. This emergency power supply provides up to 90 minutes of backup power in the case of power loss and emergency.

25 or 40W 120-347VAC input emergency battery backup inverter with 170VDC output. This compact design is a contractor favorite featuring a quick and easy installation with a single junction both for mains and backup power

 

Armour logos3

 
 



  1. PRODUCT VARIATIONS
  2. FEATURES
  3. SELF DIAGNOSTIC
  4. OPERATION
  5. SPECIFICATIONS
  6. APPLICATIONS
  7. COMPLIANCE
 
Product Code

Example EM-HBM cat. 25.WW

 MODEL NO WATTAGE TEST SWITCH
EM-HBM 25 25W / 170VDC  WW Wired
Up to 150W Driver WL 2.4GHz Remote
40 40W / 170VDC 
Up to 300W Driver
 
NOTES
¹ The emergency driver is not compatible with non-dimmable fixtures when the driver wattages is less than the fixture wattage. 
 
Features
 
  • Single input mains services both normal and emergency output
  • Constant power output in emergency mode.
  • One piece design with IP65 steel housing
  • 2 in 1 waterproof LED test switch and indicator light included, 2.4G wireless mode as optional
  • Evaluated to UL 924 requirements
 
Self Diagnostic
 
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30 second and annual 90 minute tests to verify proper emergency capability per life safety code requirements NFPA 101 Life Safety Code outlines the following schedule:
 
Monthly
During AC mode, the system conducts a 30s self discharge test of the emergency LED driver every 30 days and automatically restores to normal charging after full discharge
 
Annually
During AC mode, the system conducts a 90 minute self discharge test of the emergency led driver every 365 days and automatically restores to normal charging after 30 seconds discharge
 
Operation
 
Normal Supply
During normal AC supply conditions the LED driver load will operate as usual and emergency driver remains in charging mode
 
Emergency Mode
When AC power fails the driver automatically switches to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. During this time, the indicator will flash slowly (light on for 2 seconds, off for 2 seconds). When AC power is restored, it will return to charging mode and the indicator light remains on
 
Specification
 
Input Voltage: 120-347VAC 50/60Hz
Input Power: 10W Max
Output Voltage: 170VDC
Output Current: 0.1A
Power Factor: 0.85
EMI (Radiated and Conducted): FCC Class A Charge and EM Modes
Surge protection: Meets ANSI/IEEE C62.41.2-2002
Approval: cUL Listed for Factory and Field Installation
Emergency Operation: 90min
Operating Temp: 23° to 131°F
Battery: Li ION
 
 
Applications
 
Round and linear suspended highbays
 
 
Compliance
 
UL 924 Damp Location Listed
NFPA 101 Life Safety Code
NFPA 70 National Electrical Code
 

Similar Products

 
Argo1

EM-EMA


Integrated Emergency Driver
Lumina 1

EM-EMB


High Output Emergency Driver
Hawk Eye13

EM-EMS


Split Emergency Driver
Armour Plus13

EM-WPA


External Emergency Driver
Armour Plus13

EM-HBM


Highbay Emergency Driver

Logo Solid Shape Layer 2

100 Duffy Ave. Hicksville NY 11801 — United States +1 917 563 7078