Split Emergency Driver

The EM-EMS series emergency LED driver is for field and factory installation that allows any Sunled 0-10V dimmable fixture to be used for both normal and emergency operation.

The unit contains a battery charger and inverter that operates a load of 8W or 18W with constant power at a rated output voltage of 170VDC. The patented constant power circuitry of the module maintains uninterrupted illumination levels during power failure

 

Armour logos3

 
 


  1. PRODUCT VARIATIONS
  2. FEATURES
  3. SELF DIAGNOSTIC
  4. OPERATION
  5. SPECIFICATIONS
  6. APPLICATIONS
 
Product Code

Example EM-EMS cat. 18.WW

 MODEL NO WATTAGE TEST SWITCH
EM-EMS 8 8W / 170VDC  WW Wired
Up to 100W Driver WL 2.4GHz Remote
18 18W / 170VDC 
Up to 200W Driver
 
NOTES
¹ The emergency driver is not compatible with non-dimmable fixtures when the driver wattages is less than the fixture wattage. 
 
Features
 
  • Constant power output in emergency mode
  • Split two piece design with smaller dimensions for integral enclosures
  • Self-sensing output voltage circuitry maximises product compatibility
  • High temperature recyclable lithium battery technology enables significantly decreased enclosure size and longer operational life
  • Quick connect junction box on driver side reduces installation time
 
Self Diagnostic
 
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30 second and annual 90 minute tests to verify proper emergency capability per life safety code requirements NFPA 101 Life Safety Code outlines the following schedule:
 
Monthly
During AC mode, the system conducts a 30s self discharge test of the emergency LED driver every 30 days and automatically restores to normal charging after full discharge
 
Annually
During AC mode, the system conducts a 90 minute self discharge test of the emergency led driver every 365 days and automatically restores to normal charging after 30 seconds discharge
 
Operation
 
Normal Supply
During normal AC supply conditions the LED driver load will operate as usual and emergency driver remains in charging mode
 
Emergency Mode
When AC power fails the driver automatically switches to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. During this time, the indicator will flash slowly (light on for 2 seconds, off for 2 seconds). When AC power is restored, it will return to charging mode and the indicator light remains on
 
Specification
 
Input Voltage: 120-347VAC 50/60Hz
Input Power: 7W Max
Output Voltage: 170VDC
Input Current: 100mA
Output Power: 8,18W Power Factor: 0.85
EMI Radiated/Conducted: FCC Class A Charge and EM Modes
Surge Protection: Line-Neutral 3kV
Emergency Operation: 90 minutes
Charge Time: 24hr Recharge
Ambient Temperature: Lithium 5°C to +50°C (41°F to 122°F)
Approval: cUL Listed for Factory and Field Installation
 
 
Applications
 
Canopy, indoor and outdoor linear, wall pack
 

Similar Products

 
Argo1

EM-EMA


Integrated Emergency Driver
Lumina 1

EM-EMB


High Output Emergency Driver
Hawk Eye13

EM-EMS


Split Emergency Driver
Armour Plus13

EM-WPA


External Emergency Driver
Armour Plus13

EM-HBM


Highbay Emergency Driver

Logo Solid Shape Layer 2

100 Duffy Ave. Hicksville NY 11801 — United States +1 917 563 7078